|
Key Findings of NIST’s June 2004
Progress Report on the Federal Building and Fire Safety
Investigation of the World Trade Center Disaster
The findings
address four objectives. These are:
- To determine
(a) why and how the WTC 1 and WTC 2 collapsed following the
initial impact of the aircraft, and (b) why and how the 47-story
WTC 7 collapsed;
- To determine
why the loss of life and injuries were so low or so high depending
on location, including technical aspects of fire protection,
occupant behavior, evacuation and emergency response;
- To determine
the procedures and practices which were used in the design,
construction, operation and maintenance of the WTC buildings;
and
- To identify,
as specifically as possible, areas in national building and fire
codes, standards and practices that warrant revision.
The following
must be considered when reviewing the interim findings:
- Buildings are
not specifically designed to withstand the impact of fuel-laden
commercial airliners. While documents from the Port Authority of
New York and New Jersey (PANYNJ) indicate that the impact of a
Boeing 707 flying at 600 miles per hour, possibly crashing into
the 80th floor, was analyzed during the design of the WTC towers
in February/March 1964, the effect of subsequent fires was not
considered. Building codes do not require building designs to
consider aircraft impact.
- Buildings are
not designed for fire protection and evacuation under the
magnitude and scale of conditions similar to those caused by the
terrorist attacks of Sept. 11, 2001.
- The load
conditions induced by aircraft impact and the extensive fires on
Sept. 11, 2001, which triggered the collapse of the WTC towers,
fall outside the norm of design loads considered in building
codes.
- Prior
evacuation and emergency response experience in major events did
not include the total collapse of tall buildings such as the WTC
towers and WTC 7 that were occupied and in everyday use; instead,
that experience suggested that major tall building fires result in
burnout conditions, not global building collapse.
- The PANYNJ
was created as an interstate entity, under a clause of the U.S.
Constitution permitting compacts between states, and is not bound
by the authority of any local, state or federal jurisdiction,
including local building and fire codes. The PANYNJ’s
long-standing stated policy is to meet, and where appropriate,
exceed the requirements of local building and fire codes.
Collapse
of the WTC Towers – Working Hypothesis
NIST is
interested in determining how and why WTC 1 stood nearly twice as
long as WTC 2 before collapsing (103 minutes versus 56 minutes),
even though they were hit by virtually identical aircraft. In
addition, NIST is interested in determining what factors related to
normal building and fire safety considerations not unique to the
terrorist attacks of Sept. 11, 2001, if any, could have delayed or
prevented the collapse of the WTC towers.
The
NIST investigation team has formulated the following chronological
sequence of major events leading to the eventual collapse of the
towers:
- Aircraft
impact damaged the perimeter columns, causing redistribution of
column loads to adjacent perimeter columns and to the core columns
via the hat truss (the steel structure that supported the antenna
atop the towers and was connected to the core and perimeter
columns).
- After
breaching the building’s exterior, the aircraft continued to
penetrate into the buildings, damaging core columns with
redistribution of column loads to other intact core and perimeter
columns via the hat truss and floor systems.
- The
subsequent fires, influenced by the post-impact condition of the
fireproofing, weakened columns and floor systems (including those
that had been damaged by aircraft impact), triggered additional
local failures that ultimately led to column instability.
- Final column
instability resulted when redistributing loads could not be
accommodated any further.
Among the
factors relevant to the condition and collapse of the WTC towers –
and currently under analysis – were:
- The
innovative structural system at the time
they were built, incorporating many new and unusual features,
including:
 |
a composite floor system, using open-web bar joist
elements, and |
 |
the use
of wind tunnel testing to estimate lateral wind loads in the
design; |
- The
relative roles of the aircraft impacts and subsequent
fires;
- The
post-impact condition of the fireproofing on the floor
systems; and
- The
qualities and properties of the structural steel
used.
Following are
key points related to each of the four relevant factors:
Innovative
Structural System
- The fire
protection of a truss-supported floor system by directly applying
spray-on fireproofing was innovative and not consistent with
prevailing practice at the time of construction.
- The
fireproofing thickness (specified to meet a 2-hour fire endurance
rating) was 1/2 inch at construction and was upgraded on some
floors to 1-1/2 inches prior to Sept. 11, 2001.
- Unrelated to
the WTC buildings, a model code evaluation system service
recommended in June 2001 a minimum thickness of 2 inches for a
similar floor system to achieve the 2-hour fire rating.
- The
three-to-four-fold difference (between 1/2 inch and 2 inches) in
specifying the fireproofing thickness to meet the required fire
rating is extraordinarily large and confirms the lack of
technical basis in selecting a thickness.
- While the
building designers recognized the benefits of conducting a
full-scale fire endurance test to determine the required
fireproofing thickness, no such tests were conducted on the floor
system used in the WTC towers (NIST will be conducting this test
later this summer).
- If a
“structural frame” approach (considering that the floor truss was
connected to the interior and perimeter columns, essentially
forming a single structural unit) had been used, the needed fire
rating would likely have been 3 hours, as it was for the perimeter
columns alone.
- NIST computer simulations indicate that flames
in a given location lasted about 20 minutes before spreading to
adjacent, yet unburned combustibles, and that this spread was
generally continuous because of the even
distribution of combustibles throughout the floors and the lack of
interior partitions.
- The results
of two sets of wind tunnel tests on the WTC towers conducted by
independent laboratories in 2002 and provided to NIST show large
differences – as much as 40 percent – in resultant forces on the
structures. Additionally, the wind loads estimated from these
tests are about 20-60 percent higher than those apparently used in
the original design of the WTC towers.
- Wind load capability is a key factor in
determining the overall strength of a tall building and important
in determining its ability to withstand not only winds but also
its reserve capacity to withstand unanticipated events such as a
major fire or impact damage.
- NIST is
conducting an independent analysis to establish the baseline
performance of the WTC towers under the original design wind loads
and will compare those wind load estimates with the
then-prevailing code requirements.
Relative
Roles of Aircraft Impact and Fires
- The two WTC
towers withstood the initial impact of virtually identical
aircraft (Boeing 767 200ER) during the terrorist attacks of Sept.
11, 2001. The robustness of the perimeter structural
system and the large dimensional size of the WTC towers helped the
buildings withstand the aircraft impact.
- Following
impact, the WTC towers displayed and withstood vibrational forces
that were as much as half the levels (in extreme wind conditions)
for which the buildings were designed.
- Preliminary
aircraft impact damage analysis indicates that the impact of a
fuel filled wing section resulted in extensive damage to the
exterior wall panel, including complete failure of the perimeter
columns.
- Fires played a major role in further reducing
the structural capacity of the buildings, initiating
collapse. While aircraft impact damage did not, by
itself, initiate building collapse, it contributed greatly to the
subsequent fires by:
 |
compromising the sprinkler and water supply
systems; |
 |
dispersing jet fuel and igniting building contents over
large areas; |
 |
creating
large accumulations of combustible matter containing aircraft
and building contents; |
 |
increasing the air supply into the damaged buildings
that permitted significantly higher energy release rates than
would normally be seen in ventilation-limited building fires,
allowing the fires to spread rapidly within and between
floors; and; |
 |
damaging
ceilings that enabled “unabated” heat transport over the floor
to ceiling partition walls and to structural
components. |
- The jet fuel,
which ignited the fires, was mostly consumed within the first few
minutes after impact. The fires that burned for almost the entire
time that the buildings remained standing were due mainly to
burning building contents and, to a lesser extent, aircraft
contents, not jet fuel.
- The typical WTC office workstation furnishings
were able to sustain intense fires for at least an hour on a given
WTC floor.
Role of
Fireproofing Conditions
- Most of the
floor systems in WTC 1 impacted by the aircraft crash and fires
had upgraded or thicker (1-1/2 inches) fireproofing while most of
the affected floors in WTC 2 had the original (1/2-inch)
thickness.
- The response
of a structural component to fire is sensitive to variability in
fireproofing thickness along its length.
- As applied –
both in the original spraying and in later upgrades – the
fireproofing was found to be thermally equivalent to uniform
thicknesses that were greater than the specified minimums required
by the building owner.
- It was found
that the acceleration of a structural component would have to be
about 100-150 times the acceleration due to gravity to dislodge
1-inch-thick fireproofing similar to that used in the WTC towers.
NIST is currently conducting analytical studies to estimate the
magnitude of accelerations of the structural components due to
aircraft impact. This will help identify those regions where
fireproofing may have been dislodged.
Analysis of
Recovered WTC Steel
- The
collection of 236 pieces of steel in NIST’s possession is adequate
for analyzing the quality and properties of the steel for the
investigation, emphasizing regions of impact and fire damage.
Pieces of all specified grades of steel (for the exterior panels,
core columns and steel trusses in the floor systems) were
acquired.
- Analysis of the recovered steel indicates that
each of the structural components of the WTC towers had the grade
specified in the design drawings.
- Metallography
and mechanical property tests indicate that the strength and
quality of the steel was as specified, typical of the era and
likely met all qualifying test requirements.
- The
room-temperature strength of the steel used in the towers met the
relevant standards and, in many instances, exceeded the
requirements by 5-10 percent.
- Analysis is
ongoing of the performance of the steel components under impact
and fire conditions up to the starting point of the total building
collapse.
Collapse
of WTC 7 – Working Hypothesis
NIST is
interested in determining why and how the 47-story WTC 7 building, a
more typical tall building, collapsed even though it was not
directly hit by an aircraft.
The NIST
investigation team has formulated the following chronological
sequence of major events leading to the eventual collapse of WTC
7:
- An initial
local failure at the lower floors (below Floor 13) of the building
due to fire and/or debris induced structural damage of a critical
column (the initiating event), which supported a large span floor
bay with an area of about 2,000 square feet.
- Vertical
progression of the initial local failure up to the east penthouse,
as large floor bays were unable to redistribute the loads,
bringing down the interior structure below the east
penthouse.
- Horizontal
progression of the failure across the lower floors (in the region
of Floors 5 and 7, that were much thicker than the rest of the
floors), triggered by damage due to the vertical failure,
resulting in the disproportionate collapse of the entire
structure.
The working
hypothesis is consistent with all evidence currently held by NIST,
including photographs and videos, eyewitness accounts and emergency
communication records.
Based on a
review of the fuel system for emergency power in WTC 7, Floor 5 –
which did not have any exterior windows and contained the only
pressurized fuel distribution system on the south, west and north
floor areas – is considered a possible fire initiation location,
subject to further data and/or analysis that improve knowledge of
fire conditions in this area.
Evacuation and Emergency Response
NIST is
interested in determining what factors related to normal building
and fire safety considerations, if any, could have saved additional
WTC occupant lives on Sept. 11, 2001, or could have minimized the
loss of life among the first responders.
Evacuation
Based on
information and data gathered during the first-person interviews of
WTC surviving occupants, the following was
learned:
- It is
estimated that 17,400 occupants (± 1,200) were present in the WTC
towers on the morning of Sept. 11, 2001. The initial population of
each tower was similar.
- About 6
percent of the surviving occupants reported a pre-existing
limitation to their mobility. These limitations included obesity,
heart condition, needing assistance to walk, pregnancy, asthma,
being elderly, chronic condition, recent surgery or injury, and
other.
- About 7
percent of the surviving occupants reported having special
knowledge about the building. These included fire safety staff,
floor wardens, searchers, building maintenance and security staff.
- Two-thirds of
surviving occupants reported having participated in a fire drill
in the 12 months prior to Sept. 11, 2001, while 17 percent
reported that they received no training during that same period.
Of those participating in fire drills, 93 percent were instructed
about the location of the nearest stairwell. Overall, slightly
over half of the survivors, however, had never used a stairwell at
the WTC prior to Sept. 11, 2001.
- Approximately
87 percent of the WTC tower occupants, including more than 99
percent of those below the floors of impact, were able to evacuate
successfully.
- Rough
estimates indicate that about 20 percent or more of those who were
in the WTC towers and lost their lives may have been alive in the
buildings just prior to their collapse.
- Overall,
about 7,900 survivors evacuated WTC 2 in 73 minutes (i.e. from the
instant the WTC 1 was struck by aircraft until WTC 2 collapsed)
while about 7,500 survivors evacuated WTC 1 in 103 minutes. Thus,
the overall evacuation rate in WTC 2 (108 survivors per minute)
was about 50 percent faster than that in WTC 1 (73 survivors per
minute). Functioning elevators allowed many survivors to evacuate
WTC 2 prior to aircraft impact. Most of the elevators in WTC 1
were not functioning, and survivors could only use the stairways.
- After the
first airplane struck WTC 1 and before the second airplane struck
WTC 2, the survivors in WTC 2 were twice as likely as those in WTC
1 to have already exited the building (41 percent versus 21
percent). The rate of evacuation completion in WTC 2 was twice the
rate in WTC 1 during that same period.
- Soon after
the airplane struck WTC 2 until about 20 minutes before each
building collapsed, the survivors in WTC 2 and WTC 1 had exited at
about the same rate (the prior evacuation rate of WTC 1).
- During the
last 20 minutes before each building collapsed, the evacuation
rate in both buildings had slowed to about one-fifth the
immediately prior evacuation rate. This suggests that
for those seeking and able to reach and use undamaged exits and
stairways, the egress capacity (number and width of exits and
stairways) was adequate to accommodate
survivors.
Based on use of
existing egress models and actual evacuation time on Sept. 11, 2001,
it is estimated that a full capacity evacuation of each
WTC tower with 25,000 people – three times the number present on
Sept. 11, 2001 – would have required about 4 hours.
To
achieve a significantly faster total evacuation at full capacity
would have required increases in egress capacity (number and width
of exits and stairways).
Emergency
Communication Systems
The analysis of
the emergency responder communication tapes from Sept. 11, 2001,
indicates that:
- After the
first aircraft struck WTC 1, there was an approximate
factor of 5 peak increase in traffic level over the
normal level of emergency responder radio
communications, followed by an approximate factor of
3 steady increase in the level of subsequent traffic.
- A surge in
communications traffic volume made it more difficult to handle the
flow of communications and delivery of information.
Roughly a third to a half of the radio messages
transmitted during these radio traffic surge conditions were not
complete messages or understandable.
- The Fire
Department of New York’s (FDNY) citywide high-rise Channel 7 (PAPD
Channel 30) radio repeater at the WTC site was
operating.
- New York
Police Department (NYPD) aviation unit personnel reported critical
information about the impending collapse of the WTC towers several
minutes prior to their collapse. No evidence has been
found to suggest that the information was further communicated to
all emergency responders at the scene.
Command and
Control
Based on
face-to-face interviews, NIST has determined that first
responders – including key incident commanders – did not have
adequate information (voice, video and data) on, nor an overall
perspective of, the conditions in the WTC buildings and what was
happening elsewhere at the WTC site. Interagency information sharing
was inadequate.
Active Fire
Protection Systems
Investigation of
the design, capabilities and performance of the active fire
protection systems in the WTC towers and WTC 7 indicates
that:
- The smoke
management systems in the WTC towers were not activated during the
fires on Sept. 11, 2001, likely due to damage inflicted by the
aircraft impacts.
- HVAC
(heating, ventilation, and air-conditioning) ductwork was a major
path for vertical smoke spread in the buildings.
- Computer
modeling shows that stair pressurization systems would have
provided minimal resistance to the passage of smoke in WTC 1 and
WTC 2 had they been installed on Sept. 11, 2001.
- The fire
alarm system in WTC 7 sent only one signal (at 10:00:52 a.m.
shortly after the collapse of WTC 2) to the monitoring company
indicating a fire condition. The signal did not contain any
specific information about the location of the fire within the
building. Since the system was placed on TEST for a period of 8 h
beginning at 6:47:03 a.m. on September 11, 2001, alarm signals
would not have been shown on the operator’s display; instead, they
would have to be recorded into the history file.
- The
resistance to failure of the fire alarm system communications
paths between the fire command station and occupied WTC tower
floors could have been enhanced if fiber optic communications
cable had been used instead of copper lines.
- Although the
fire sprinkler system was damaged by aircraft impact,
the water supply riser system lacked redundancy and
there existed the potential for single point failure of the water
supply connection on each floor.
Procedures and Practices
NIST seeks to
determine the building and fire safety procedures and practices that
were used over the life of the WTC buildings and how well those
procedures and practices conformed to accepted national building and
fire safety practices, standards and codes.
Applicable
Building Codes
The Port
Authority of New York and New Jersey (PANYNJ) adopted the provisions
of the proposed 1968 edition of the New York City Building Code,
more than three years before it went into effect. The 1968 edition
allowed the PANYNJ to take economic advantage of less restrictive
provisions compared with the 1938 edition that was in effect when
design began for the WTC towers in 1962. The 1968 code:
- Eliminated a
“fire tower” (a smoke-free stairwell) as a required means of
egress;
- Reduced the
number of required stairwells from 6 to 3, and the size of doors
leading to the stairs from 44 inches to 36 inches;
- Reduced the
fire rating of the shaft walls in the building core from 3 hours
to 2 hours;
- Changed
partition loads from 20 pounds per square foot to one based on
weight of partitions per unit length (that reduced such loads for
many buildings including the WTC buildings); and
- Permitted a
1-hour reduction in fire rating for all structural components
(columns from 4 hours to 3 hours and floor framing members from 3
hours to 2 hours).
The New York
City Department of Buildings reviewed the WTC tower drawings in 1968
and provided comments to the PANYNJ concerning the plans in relation
to the 1938 NYC building code. The architect-of-record submitted
responses to those comments to the PANYNJ, noting how the drawings
conformed to the 1968 NYC building code.
Standards,
Codes and Regulations
NIST has
reviewed past and current standards, codes and regulations relevant
to assessing the procedures and practices used in the design,
construction, operation and maintenance of the WTC buildings.
Based on that review, the following issues merit further
consideration:
- Code
provisions with detailed procedures to analyze and evaluate data
from fire resistance tests of other building components and
assemblies to qualify an untested building element.
- Code
provisions that require the conduct of a fire resistance test if
adequate data do not exist from other building components and
assemblies to qualify an untested building element.
- Regulations
that would adopt code provisions using the “structural frame”
approach to fire resistance ratings that requires structural
members – other than columns – that are essential to the stability
of the building as a whole to be fire protected to the same rating
as columns.
- Code
provisions that ensure that structural connections are provided
the same degree of fire protection as the more restrictive
protection of the connected elements.
- Code
provisions and standards to establish whether the minimum
mechanical and durability related properties of spray-applied fire
resistive materials (SFRM) are sufficient to ensure acceptable
in-service performance in buildings. While minimum bond strength
requirements exist, there are no requirements for such materials
to withstand typical shock, impact, vibration or abrasion effects
over the life of a building.
- Rigorous
field application and inspection provisions and regulatory
requirements to assure that the as-built condition of the passive
fire protection, such as SFRM, conforms to conditions found in
fire resistance tests of building components and
assemblies.
- Rigorous
provisions and regulatory requirements for in-service inspections
of passive fire protection during the life of the building.
- Early
installation of sprinklers in existing buildings, not as an option
in lieu of compartmentation (office space separated by internal
walls).
- Standards and
code provisions that provide minimum structural integrity to
protect the means of egress (stairwells and elevator shafts) in
the building core which are critical to life safety.
- Standards and
code provisions to install fire-protected elevators and permit
their use for routine emergency access by first responders or as a
secondary method (after stairwells) for emergency evacuation of
building occupants.
- Explicit
standards and code provisions for structural integrity that
mitigate progressive collapse.
- Standards and
code provisions for conducting wind tunnel tests and for the
methods used in practice to estimate design wind loads from test
results.
- Regulatory
requirements for retention of documents related to the design,
construction, operation, maintenance and modifications of
buildings, including retention off-site.
Fire Safety
and Egress Design Methods
Performance-based methods that explicitly define the design
objectives and specific design-basis fire hazards or evacuation
events are better suited to risk analysis than traditional
prescriptive methods of deriving code provisions and standards.
Historical fire loss data suggest that prescriptive methods have
considerable built-in conservatism to adequately protect building
occupants. Performance-based methods enable appropriate protection
to be provided where it is needed.
The
increasing use of performance-based methods, as an alternative to
prescriptive design, in fire safety and egress design, raises the
following issues that merit further
consideration:
- Considering
fire as a design condition in structural design, including
evaluation of the fire performance of the structure as a whole
system. This is already done with other hazards such as wind and
earthquakes.
- Detailing
procedures to select appropriate design-basis fire scenarios for
performance-based design of the sprinkler system, compartmentation
and passive protection of the structure.
- Validating
and verifying tools for use in performance-based design practice
to analyze the dynamics of building fires and their effects on the
structural system that would allow engineers to evaluate
structural performance under alternative fire scenarios and fire
protection strategies.
- Developing
the technical basis to establish whether the construction
classification and fire rating requirements are risk-consistent.
Specifically, it is not apparent how the current height and area
tables in building codes consider the technical basis for the
progressively increasing risk to an occupant on the upper floors
of tall buildings that are much greater than 200 ft in height. The
maximum fire rating in current codes applies to any building more
than about 12 stories in height.
- While
sprinklers improve safety in most common building fires and
prevent them from becoming large fires, the technical basis is not
available to establish the sprinkler trade-off in current codes
which allows a lower fire rating to be used for structural
components in spinklered buildings.
- Designing
egress systems to achieve a target performance (e.g., evacuation
rate or time) for a given occupant population by adequately
considering travel distance, remoteness requirements, and human
factors (such as occupant size, stairwell environmental
conditions, visibility and congestion).
Building
Practices
The PANYNJ
entered into agreements with the NYC Department of Buildings (DOB)
in the 1990s with regard to conformance of its buildings to the NYC
Building Code. However, the PANYNJ did not yield jurisdictional
authority for regulatory and enforcement oversight to the DOB. The
PANYNJ was created as an interstate entity and is not bound by the
authority of any local, state or federal jurisdiction.
The
architect is responsible for specifying the fire protection in
current building practice. The structural engineer is not required
to evaluate and certify that the passive fire protection is adequate
to protect the structural system. In accordance with established
practice, the structural engineer was not responsible for the
passive fire protection in the design of the WTC tower structures.
In addition,
there is no requirement to involve a fire protection engineer in the
design and evaluation of a building’s fire protection system. In
some cases, architects retain fire protection engineers to assist
with the fire protection design for a building.
There are few
academic degree programs or continuing education programs that
qualify engineers (or architects) to evaluate the fire performance
of structures. The current state-of-practice is not sufficiently
advanced for engineers to routinely analyze the performance of a
whole structural system under a prescribed design-basis fire
scenario.
Approach
to Recommendations
NIST does not
set building codes and standards but provides technical support to
the private sector and other government agencies in the development
of U.S. building and fire practices, standards and codes. NIST
recommendations are given serious consideration by private sector
organizations that develop national standards and model codes –
which provide minimum requirements for public welfare and
safety.
The NIST
building and fire safety investigation of the WTC disaster has not
yet formulated recommendations. However, in doing so, NIST will
consider the following:
- Findings from
the first three independent investigation objectives related to
building performance, evacuation and emergency response, and
procedures and practices.
- Whether
findings relate to the unique circumstances surrounding the
terrorist attacks of Sept. 11, 2001, or to normal building and
fire safety considerations, including evacuation and emergency
response.
- What
technical solutions are needed, if any, to address potential risks
to buildings, occupants, and first responders, considering both
identifiable hazards and the consequences of those hazards.
- Whether the
risk is in all buildings or limited to certain building types
(such as height and area or structural system), buildings that
contain specific design features, iconic/signature buildings or
buildings that house critical functions.
Date created:
6/18/2004 Last updated: 6/18/2004 Contact:mailto:inquiries@nist.gov
|